ICS/OT Vulnerability Disclosures for Airleader Master, Hitachi Energy SuprOS, and WAGO Industrial Switches
Vulnerability Disclosure · 2 sources · Updated 5mo ago · First seen Feb 13, 2026

CISA published an ICS advisory for Airleader GmbH Airleader Master identifying CVE-2026-1358, a critical (CVSS 9.8) unrestricted file upload issue (CWE-434) affecting versions 6.381 and earlier. The advisory states that multiple web pages running with maximum privileges allow unauthenticated file uploads without restriction, which could enable remote code execution on the server; the issue was reported by SySS GmbH.
CISA also issued an ICS advisory for Hitachi Energy SuprOS describing a default credentials weakness (CWE-1392) affecting SuprOS 9.2.1 and below and 9.2.2.0 (listed as CVE-2025-7740, CVSS 8.8), where an admin account created during deployment could be abused by an attacker with local authenticated access, impacting confidentiality, integrity, and availability. Separately, CERT@VDE warned of multiple critical vulnerabilities in WAGO 852 series Industrial Managed Switches (models 8052-1322 and 0852-1328, firmware 2.64 and prior), including CVE-2026-22906 (hardcoded key enabling decryption of AES-ECB–protected stored credentials if a configuration file is obtained) and cookie-parsing flaws such as CVE-2026-22904 that can be triggered remotely via oversized cookie values, enabling denial of service and potentially code execution through the web management interface (modified lighttpd and custom CGI binaries).
Why it matters
Impact assessment
These disclosures affect industrial control and operational technology environments using Airleader Master, Hitachi Energy SuprOS, and WAGO 852-series managed switches, with exposure spanning multiple critical infrastructure sectors and worldwide deployments. The most severe risk is unauthenticated remote compromise of Airleader Master and potentially remote denial of service or code execution against WAGO web management interfaces, while Hitachi SuprOS presents a serious privilege-abuse risk where local authenticated access exists.
Severity and scope
- Airleader GmbH Airleader Master is used in Chemical, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, and Water and Wastewater sectors.
- Airleader Master deployments are described as worldwide.
- CVE-2026-1358 in Airleader Master is critical, with potential for unauthenticated remote code execution on the server.
- Hitachi Energy SuprOS is used in Energy, Transportation Systems, and Government Services and Facilities.
- SuprOS deployments are described as worldwide.
- CVE-2025-7740 in SuprOS can affect confidentiality, integrity, and availability through abuse of an admin account created during deployment.
- WAGO 852 series Industrial Managed Switches are affected at the network infrastructure layer of OT environments, increasing the risk of operational disruption if exploited.
- WAGO cookie-parsing flaws can cause denial of service and may enable code execution through the web management interface.
Exploitation status
- CISA states there is no known public exploitation specifically targeting CVE-2026-1358 at the time of publication.
- The provided references do not report in-the-wild exploitation for CVE-2025-7740.
- The provided story text does not cite active exploitation for the WAGO issues.
Business impact
- Successful exploitation could disrupt industrial operations, impair visibility or control functions, and create downstream safety and availability concerns in OT environments.
- Compromise of management interfaces or administrative accounts could enable unauthorized configuration changes, credential exposure, lateral movement, and prolonged persistence in segmented industrial networks.
- Because affected products are deployed across critical infrastructure sectors, exposure should be treated as high-priority even without confirmed mass exploitation.