CISA ICS advisories disclose multiple critical-manufacturing vulnerabilities in Hitachi Energy, Ilevia, and Open62541
Vulnerability Disclosure · 4 sources · Updated 5mo ago · First seen Feb 5, 2026

CISA published multiple ICS advisories affecting critical manufacturing environments, including a critical RADIUS forgery weakness impacting Hitachi Energy XMC20 and FOX61x when configured for remote RADIUS authentication. The issue (tracked as CVE-2024-3596, CVSS v3.1 9.0) stems from the RADIUS protocol’s use of an MD5 Response Authenticator, enabling a local attacker to perform a chosen-prefix collision and alter server responses (e.g., Access-Accept, Access-Reject, Access-Challenge), with potential confidentiality, integrity, and availability impact.
Separately, CISA warned that Ilevia EVE X1 Server (<= 4.7.18.0) contains multiple vulnerabilities (including CVE-2025-34183/34184/34185/34186/34187 and CVE-2025-34512/34513/34517/34518) that can enable pre-auth file disclosure (via the db_log POST parameter) and unauthenticated OS command injection (in /ajax/php/login.php), potentially leading to arbitrary command execution and sensitive information exposure; at least one issue is scored CVSS 9.8. CISA also disclosed an out-of-bounds write in o6 Automation GmbH Open62541 (CVE-2026-1301, CVSS 5.7) where, with PubSub and JSON enabled, a crafted JSON message can trigger pre-auth memory corruption and a reliable denial of service.
Why it matters
Impact assessment
CISA disclosed multiple ICS vulnerabilities affecting critical manufacturing environments, with the highest immediate risk in internet-reachable or remotely administered deployments of Hitachi Energy XMC20/FOX61x and Ilevia EVE X1 Server. The Ilevia issues are the most operationally severe because several unauthenticated flaws can enable arbitrary command execution, credential exposure, authentication bypass, and potential root-level compromise; the Hitachi issues can undermine remote authentication integrity where RADIUS is used; and the Open62541 flaw can cause pre-authentication denial of service in specific builds.
Scope is broad in terms of deployment geography because all affected products are described as deployed worldwide, but practical exposure is configuration-dependent for Hitachi and Open62541. CISA states no known public exploitation was reported for the Ilevia and Open62541 issues at publication; the provided advisories do not cite in-the-wild exploitation for the Hitachi RADIUS forgery issue.
Affected entities and products
- Hitachi Energy XMC20 R18, R17A and earlier, when configured for remote RADIUS authentication
- Hitachi Energy FOX61x R18, R17A and earlier, when configured for remote RADIUS authentication
- Ilevia EVE X1 Server versions <= 4.7.18.0
- Ilevia EVE X1/X5 Server for some authentication and privilege-escalation issues noted in the advisory facts
- o6 Automation GmbH Open62541 versions >= 1.5-rc1 and < 1.5-rc2, in builds with PubSub and JSON enabled
Severity and business impact
- Hitachi Energy CVE-2024-3596: Critical, CVSS 9.0; can affect confidentiality, integrity, and availability by enabling forged RADIUS responses
- Ilevia vulnerabilities: multiple Critical issues scored CVSS 9.8; can lead to full system compromise, arbitrary OS command execution, authentication bypass, plaintext credential exposure, and privilege escalation
- Open62541 CVE-2026-1301: Medium, CVSS 5.7; reliable process crash and memory corruption can disrupt ICS services
Exposure scope and exploitation status
- Critical manufacturing sector explicitly identified across the advisories
- Worldwide deployment stated for Hitachi Energy, Ilevia, and Open62541 products
- Hitachi exposure depends on use of remote RADIUS authentication
- Open62541 exposure depends on PubSub and JSON being enabled in affected builds
- CISA reports no known public exploitation for Ilevia and Open62541 at publication
- No known exploitation is stated in the provided Hitachi advisory summaries