CVE-2025-40944: S7 Disconnect Request Denial of Service in Siemens SIMATIC/SIPLUS ET 200 Modules and PN Couplers
CVE-2025-40944 is a denial-of-service vulnerability in multiple Siemens SIMATIC and SIPLUS ET 200 interface modules and PN/MF and PN/PN couplers. Affected devices improperly handle valid S7 protocol Disconnect Requests (COTP DR TPDU) received on TCP port 102, entering an improper session state that can render them unresponsive. Exploitation requires neither authentication nor user interaction, and recovery requires a power cycle.
Impact, mitigation & remediation
What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.
Impact
What an attacker gets, and what they’ve been doing with it.
An unauthenticated attacker with network access to an affected device can cause device unavailability, potentially disrupting industrial communications and associated operations. The device can remain unresponsive until power-cycled. The vulnerability has high availability impact; no confidentiality or integrity impact is identified. Its CVSS v3.1 base score is 7.5, with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
Mitigation
If you can’t patch tonight, do this now.
Use an external firewall or equivalent access controls to restrict TCP port 102 communications to trusted machines. Segment industrial control networks from business and untrusted networks, and prevent direct internet exposure of affected devices. Protect device access according to Siemens industrial security operational guidelines and relevant product manuals. Where remote access is necessary, use maintained, secure access mechanisms such as VPNs. Retain these controls particularly for products without a planned fix.
Remediation
Patch, then assume compromise.
Install the product-specific fixed firmware: V1.3 or later for SIMATIC ET 200SP IM 155-6 PN HA, including SIPLUS variants; V6.0.1 or later for SIMATIC ET 200SP IM 155-6 PN R1; V4.2.5 or later for SIMATIC ET 200SP IM 155-6 PN/2 HF and the listed corresponding SIPLUS PN HF, T1 RAIL, and TX RAIL variants; V4.2.2 or later for SIMATIC ET 200SP IM 155-6 PN/3 HF; and V6.0.0 or later for the listed SIMATIC PN/PN and SIPLUS NET PN/PN couplers. No fix is currently planned for the listed ET 200AL IM 157-1 PN, SIMATIC/SIPLUS ET 200MP IM 155-5 PN HF variants, ET 200SP IM 155-6 MF HF, or PN/MF Coupler. Apply compensating network controls to those products. Power-cycling restores operation after exploitation but does not remediate the vulnerability.
Exploits
No public exploits tracked yet. Mallory keeps watching.
Frequently asked questions
- Is CVE-2025-40944 exploited in the wild?
- As of Nov 5, 2026, Mallory has no reports of CVE-2025-40944 being exploited in the wild. It is not listed in CISA KEV.
- Is there a public exploit for CVE-2025-40944?
- As of Nov 5, 2026, Mallory has found no public exploit for CVE-2025-40944.
- Is there a patch for CVE-2025-40944?
- Install the product-specific fixed firmware: V1.3 or later for SIMATIC ET 200SP IM 155-6 PN HA, including SIPLUS variants; V6.0.1 or later for SIMATIC ET 200SP IM 155-6 PN R1; V4.2.5 or later for SIMATIC ET 200SP IM 155-6 PN/2 HF and the listed corresponding SIPLUS PN HF, T1 RAIL, and TX RAIL variants; V4.2.2 or later for SIMATIC ET 200SP IM 155-6 PN/3 HF; and V6.0.0 or later for the listed SIMATIC PN/PN and SIPLUS NET PN/PN couplers. No fix is currently planned for the listed ET 200AL IM 157-1 PN, SIMATIC/SIPLUS ET 200MP IM 155-5 PN HF variants, ET 200SP IM 155-6 MF HF, or PN/MF Coupler.
- How severe is CVE-2025-40944?
- CVE-2025-40944 has a CVSS v4 score of 8.7 (High) and an EPSS score of 0.57% (41st percentile) as of Nov 5, 2026.
Recent activity
12 sources tracked across advisories and community write-ups. News coverage will land here when it surfaces.
No news coverage yet. Advisories and community discussion only.