CVE-2023-25915: Authenticated Remote Command Execution in Danfoss AK-SM 800A
- Vendor
- Danfoss
CVE-2023-25915 is an improper input validation vulnerability affecting all Danfoss AK-SM 800A series controllers running firmware earlier than version 3.3. An authenticated remote attacker with low privileges can supply malicious input to execute arbitrary commands in the context of the controller's web server. The affected function and precise input parameters are not specified. These controllers supervise refrigeration, HVAC, and lighting systems.
Impact, mitigation & remediation
What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.
Impact
What an attacker gets, and what they’ve been doing with it.
Successful exploitation compromises command execution within the web-server security context, potentially affecting the confidentiality, integrity, and availability of the controller and accessible resources. Controller compromise could enable unauthorized changes to refrigeration settings, defrost schedules, or alarms and disrupt cooling operations, potentially causing spoilage and operational losses. Root-level privileges are not established for this vulnerability. Known exploitation has been recorded, but its use in specific supermarket attacks is not established.
Mitigation
If you can’t patch tonight, do this now.
Remove controller management interfaces from direct internet exposure. Restrict access to authorized management systems through firewalls, source-address allowlists, and a secured VPN, and isolate controller networks from business networks. Replace default credentials and enable Strict Mode where supported as defense in depth. These measures do not replace firmware updates; the original vendor advisory specifies no vulnerability-specific workaround.
Remediation
Patch, then assume compromise.
Upgrade affected AK-SM 800A controllers to firmware version 3.3 or a later supported release using the vendor's supported update process. Danfoss advisory DSA-2023-08-01 identifies version 3.3 as the fix threshold. Prefer the latest supported firmware to address additional vulnerabilities. Coordinate maintenance with the refrigeration provider or integrator and verify the running firmware version afterward. Review access logs and controller configuration for evidence of prior compromise; updating alone does not reverse an existing intrusion.
Exploits
No public exploits tracked yet. Mallory keeps watching.
Affected products & vendors
Products and vendors Mallory has correlated with this vulnerability. Open in Mallory to drill down to specific CPE configurations and version ranges.
References
Frequently asked questions
- Is CVE-2023-25915 exploited in the wild?
- Yes. As of Nov 28, 2026, Mallory has reports of exploitation in the wild, and CISA added it to KEV on Nov 25, 2026.
- Is there a public exploit for CVE-2023-25915?
- As of Nov 28, 2026, Mallory has found no public exploit for CVE-2023-25915.
- Is there a patch for CVE-2023-25915?
- Upgrade affected AK-SM 800A controllers to firmware version 3.3 or a later supported release using the vendor's supported update process. Danfoss advisory DSA-2023-08-01 identifies version 3.3 as the fix threshold.
- What products are affected by CVE-2023-25915?
- Danfoss Ak-Sm 800a Firmware.
- How severe is CVE-2023-25915?
- CVE-2023-25915 has a CVSS v3.1 score of 8.8 (High) and an EPSS score of 2.5% (85th percentile) as of Nov 28, 2026.
Recent activity
46 sources tracked across advisories, community write-ups, and news. New activity surfaces here as Mallory finds it.