CVE-2018-8872: Arbitrary Memory Write in Schneider Electric Triconex Tricon MP Model 3008

Published May 4, 2018 · Updated 1 month ago
Trending this weekNot trendingOutside this week’s top 100
Mention activity · 30 daysNo mention activity in the last 30 days.
CVSS8.1High · v3
EPSS2.2%83rd percentile
CISA KEVNoNot listed
In the wildNoneNo exploitation reported
Vendor
Schneider Electric
IdentifiersCVE-2018-8872CWE-119 · Improper Restriction of Operations…

CVE-2018-8872 is a memory-handling vulnerability in Schneider Electric Triconex Tricon MP Model 3008 firmware versions 10.0–10.4. System calls read memory addresses directly from the control program area without verification. Manipulating this data allows attacker-controlled data to be copied to arbitrary locations in controller memory. HatMan malware targets this vulnerability alongside CVE-2018-7522 to compromise Triconex safety instrumented systems.

Do you run this?See affected versions in your environment and whether adversaries are exploiting this vulnerability against assets like yours.
Check your exposure
Analyst brief

Impact, mitigation & remediation

What it means and what to do now: patch path, interim mitigations, and the assume-compromise checklist.

Impact

What an attacker gets, and what they’ve been doing with it.

Exploitation permits arbitrary modification of controller memory, undermining firmware and control-program integrity. Exploitation of CVE-2018-8872 and CVE-2018-7522 can enable arbitrary code execution, misinform or control the safety instrumented system, cause system shutdown, or compromise safety functions. The individual contribution of CVE-2018-8872 to these broader outcomes is not separately established.

Mitigation

If you can’t patch tonight, do this now.

Isolate safety-system networks from other networks, place them behind firewalls, and prevent direct Internet accessibility. Restrict remote access and use maintained secure access mechanisms when required. Restrict physical access to controllers, use locked cabinets, and never leave controllers in PROGRAM mode. Configure operator stations to alarm when the key switch enters PROGRAM mode. Secure TriStation engineering workstations, connect them only to the safety network, and verify that connected computers and removable media are free of malware. Assess operational and safety impacts before deploying defensive changes.

Remediation

Patch, then assume compromise.

Upgrade to the latest Schneider Electric Triconex Tricon CX version with vendor assistance. Tricon CX v11.4 was identified as available with security enhancements addressing HatMan techniques and other sophisticated attacks; it is not explicitly established as the first fixed version for CVE-2018-8872. For suspected compromise, engage Schneider Electric support to collect and analyze controller data and perform necessary malware removal procedures.

Public exploits

Exploits

No public exploits tracked yet. Mallory keeps watching.

View more in app →
No public exploit code observed for this vulnerability. Mallory keeps watching.
Exposure surface

Affected products & vendors

Products and vendors Mallory has correlated with this vulnerability. Open in Mallory to drill down to specific CPE configurations and version ranges.

VendorProductType
Schneider ElectricTriconex Tricon Mp 3008 Firmwareoperating_system
FAQ

Frequently asked questions

Is CVE-2018-8872 exploited in the wild?
As of Oct 16, 2026, Mallory has no reports of CVE-2018-8872 being exploited in the wild. It is not listed in CISA KEV.
Is there a public exploit for CVE-2018-8872?
As of Oct 16, 2026, Mallory has found no public exploit for CVE-2018-8872.
Is there a patch for CVE-2018-8872?
Upgrade to the latest Schneider Electric Triconex Tricon CX version with vendor assistance. Tricon CX v11.4 was identified as available with security enhancements addressing HatMan techniques and other sophisticated attacks; it is not explicitly established as the first fixed version for CVE-2018-8872.
What products are affected by CVE-2018-8872?
Schneider Electric Triconex Tricon Mp 3008 Firmware.
How severe is CVE-2018-8872?
CVE-2018-8872 has a CVSS v3 score of 8.1 (High) and an EPSS score of 2.2% (83rd percentile) as of Oct 16, 2026.
Mallory platform

The version that knows your environment.

This page is what’s public. Mallory adds the parts that aren’t: which of your assets are affected, which adversaries are exploiting it right now, and which detections to deploy tonight.
Exposure mappingQuery your assets running an affected version, and investigate the blast radius.
Threat actor evidenceEvery report linking this CVE to a named adversary.
Associated malware3Malware families linked to this CVE, with evidence and IOCs.
Detection signaturesYARA, Sigma, Snort, and vendor rules, auto-deployed to your SIEM.
Vendor-by-vendor mappingCross-references every affected SKU, including bundled OEM variants.
Social activityCommunity discussion across Reddit, Mastodon, and other social sources.